Check whether yours is affected, then follow the instructions below.
The power can stay on when the safety switch handle is in the "OFF" position, posing an electrical shock or electrocution hazard to consumers.
The Recall Registry rates this worth checking — we found nothing in the notice describing a specific injury. A recall covers only the versions, UPCs or date codes it names, so check those against yours.
Photos help. Identifiers decide. Appearance can vary by color, finish or packaging. Confirm the model number, date code or other identifier in the official notice.

Recall image provided by CPSC

Consumers should immediately inspect installed safety switches by moving the handle to the "OFF" position. If the power stays on when the handle is in the "OFF" position, contact Schneider Electric for a free replacement safety switch and free service support to install the replacement switch. If the safety switch is not installed and included in the recall, contact Schneider Electric for a free replacement safety switch. Instructions on how to inspect the switch can be found at www.schneider-electric.us/gdss-safetyalert.
Who to contact: Schneider Electric toll-free at 877-672-1953 from 8 a.m. to 5 p.m. ET Monday through Friday or online at www.schneider-electric.us/gdss-safetyalert or www.schneider-electric.com and click on “Square D” (found under Quick Links) for more information.
This recall involves Square D brand General Duty 30 & 60A, 120/240-volt, 2-phase and 3-phase NEMA 3R safety switches. The switches are a dark gray metal box with a black handle on the side that can be moved to an "ON" or "OFF" position. The "OFF" position is designed to shut off the flow of electricity. The switches may be used in or around commercial buildings, outbuildings, apartments and homes. They measure about 10 inches by 7 inches by 4 inches. Brand name "Square D", the ampere of the safety switch and the 120/240-volt or 240-volt marking is printed on a label on the front of the safety switch. The recalled switches were manufactured between January 1, 2014 through January 18, 2018 and have date codes 1401 through 1803. The date codes are in the YYWW format (example: 1401 = year 2014, week 1). The date code of the product can only be found on the inside of the cover and is not accessible if the product is installed and in-service. Only safety switches with the following catalog numbers printed on a separate label on the side are included in the recall: Catalog Number CD321NRB D211NRB D211NRBCP D221NRB D221NRBCP D221NRBUP D321NRB D321NRBCP D321NRBUP DU221RB DU221RBUP DU222RB DU222RBUP DU321RB DU321RBUP DU321RBCP DU322RB DU322RBCP DU322RBUP
Authorized Schneider Electric distributors, Home Depot, Lowe's, original equipment manufacturers and others stores nationwide and online at Amazon.com, HomeDepot.com, and Lowes.com from January 2014 through January 2018 for between $40 and $500.
This recall was issued by the U.S. Consumer Product Safety Commission. The Recall Registry summarises it — always confirm the details at the source.
Their exact wording: “Schneider Electric Recalls Square D Safety Switches Due to Electrical Shock Hazard”
Worried about the other things in your house? You can write down what you have and be told if one is recalled — or, if you sell second-hand, check your whole stock at once.
Filed under: Everything else
A loss of driver power increases the risk of a crash.